By Sebastian Grabowski, DC Fire & Security, Luton. Updated October 2026.
In blocks of flats whose top storey is over 11m, communal fire doors must be checked at least every 3 months and flat entrance doors at least every 12 months (Fire Safety (England) Regulations 2022, Regulation 10). Everywhere else, no law fixes the interval. The fire risk assessment sets it, and government guides suggest a monthly check of every fire door.
Only blocks of flats over 11m have fixed legal intervals: 3 months for communal doors and 12 months for flat entrance doors. Every other building relies on its fire risk assessment, with government guides pointing to a monthly check and BS 9999 to a professional inspection at least every 6 months.
"FRA" means fire risk assessment. Where no law sets an interval, the table says so and gives the guidance or common practice instead.
| Property type | Which doors | How often (minimum) | Where the rule comes from | Who can do it | Often missed |
|---|---|---|---|---|---|
| Flats, top storey over 11m | Communal doors: corridors, stairs, lobbies, plant rooms | At least every 3 months (law) | Fire Safety (England) Regulations 2022, Reg 10; gov.uk guidance updated Aug 2025 | Trained caretaker or staff. Repairs by a competent contractor | Riser and plant room doors. A written record of every check |
| Flats, top storey over 11m | Flat entrance doors | At least every 12 months, best endeavours (law) | Reg 10 | As above | Recording refused access. Doors swapped by leaseholders |
| Flats, 11m and under | Communal and flat entrance doors | No fixed legal interval. FRA sets it. Common practice: routine checks every 1 to 3 months, professional inspection every 6 to 12 months | Fire Safety Order 2005, Article 17 (maintenance); Reg 10 resident information still applies | Staff, plus a qualified inspector periodically | Assuming no checks are needed |
| Higher-risk residential, 18m+ or 7+ storeys | All fire doors | Same as over 11m: 3 months communal, 12 months flat doors | Reg 10 plus Building Safety Act 2022 duties on the Accountable Person | Staff, plus a qualified inspector | Keeping check and repair records in the golden thread and safety case |
| HMOs | Room doors onto the escape route, kitchen, cellar | No fixed national interval. FRA and licence conditions set it. Common practice: landlord check at each visit, professional inspection every 12 months | Housing Act 2004; HMO Management Regulations 2006, reg 4; LACORS guide; Fire Safety Order for common parts | Landlord or manager. Repairs by a competent person | Disconnected closers, painted seals, keyed locks instead of thumb-turns |
| Schools | All fire doors, especially corridor and stair doors | No fixed legal interval. Monthly check (HM Government guide). DfE blog: "at least every six months" | Fire Safety Order; educational premises guide; DfE Buying for Schools blog (2023) | Site staff monthly. A qualified inspector 6-monthly | Doors wedged open between lessons. Old doors that were never fire doors |
| Care homes | Bedroom, corridor and compartment doors | No fixed legal interval. Daily: escape-route doors close fully. Monthly: all fire doors. Annual: compartmentation | HM Government residential care guide; CQC Regulation 15 (premises) | Staff daily and monthly. A competent person annually | Hold-open devices that fail to release. Doors propped with furniture |
| Hospitals and NHS premises | All fire doors | Monthly check (HTM 05-03). Annual inspection of compartmentation. IHEEM example: planned inspection every 1 to 12 months by usage and patient dependency | HTM 05-03 Part K; IHEEM guidance (2020) | Fire wardens monthly. Estates team or inspector for planned checks | Bed and trolley damage on cross-corridor doors |
| Hotels, hostels, B&Bs | Bedroom, corridor and stair doors | No fixed legal interval. Monthly check (HM Government guide) | Fire Safety Order; sleeping accommodation guide | Staff monthly. A qualified inspector periodically | Escape-route glazing and missing closers |
| Offices, shops, factories, warehouses | All fire doors | No fixed legal interval. Monthly check (HM Government guide). BS 9999: inspect at least every 6 months | Fire Safety Order; offices and shops guide; BS 9999:2017 | Staff monthly. A qualified inspector 6-monthly | Store and plant room doors. Doors wedged for deliveries |
| Student accommodation | Flat, cluster, bedroom and corridor doors | If it is a block of flats over 11m, treat as Reg 10 (3 and 12 months). Otherwise FRA sets it, with monthly checks | Reg 10 where it applies; sleeping accommodation guide | Staff, plus a qualified inspector before each academic year | Closers and seals damaged at move-in |
| Heavily used doors, any building | Cross-corridor and stair doors | At least monthly, more often where damage is likely | HM Government guides; HTM 05-03; BS 9999; DfE blog | Staff | Closers, hinges and seals wear fastest |
A fixed schedule is law in one case only: residential buildings with a top storey over 11m, under Regulation 10 since 23 January 2023. Every other building still has a legal duty to keep fire doors in efficient working order and good repair (Fire Safety Order 2005, Article 17).
Article 17 does not say how often. The fire risk assessment should set a frequency for each door type. The government guides for care homes, schools, hotels, offices and shops all list fire doors under monthly checks. They are examples, not rules, but expect to justify doing less.
Regulation 10 also requires the Responsible Person in every block of flats with common parts, whatever its height, to tell residents to keep fire doors shut, not to tamper with closers and to report faults. New residents get this when they move in, and everyone gets a reminder at least every 12 months.
A routine check is a quick visual look that trained staff can do, the gov.uk guidance says, with no specialist or tools needed. A professional inspection is a door-by-door survey by a qualified inspector, usually every 6 to 12 months, that finds the faults a routine check misses.
Routine checks catch the obvious: a closer that no longer shuts the door, a missing seal, a wedge. A professional inspection, carried out in line with BS 8214 (revised March 2026), confirms the door is a genuine fire door, measures every gap against the 4mm industry limit, checks hinges, glazing and labels, and prices the repairs. Use our fire door inspection checklist for the routine checks and see fire door gap tolerances for the measurements.
| Routine check | Professional inspection | |
|---|---|---|
| Who | Caretaker, site staff, fire warden or landlord | A qualified fire door inspector |
| How often | Monthly to every 3 months, or as the FRA says | Usually every 6 to 12 months, or after works |
| What's checked | Door closes fully, seals present, no damage, nothing propping it open | Certification, construction, every gap measured, closers, hinges, glazing, ironmongery, signage |
| Records | Date, doors checked, faults found and reported | Door-by-door report with photos, defects and priced repairs |
Each record should show the date, who checked, which doors were checked and what was wrong. For flat entrance doors over 11m, Regulation 10 also requires you to record the steps taken to get access, including any refusal.
Records are your evidence. A fault that appears on three checks in a row with no repair is a red flag for any enforcing officer. Our demo inspection report shows what a full door-by-door record looks like.
Because doors wear out with use. In our inspections, 72% of fire doors needed at least one repair on a first visit (339 of 470 doors, September 2025 to October 2026).
Across 448 doors, gaps and alignment were the biggest fault at 39%, followed by missing, damaged or painted seals at 35%, threshold and drop seals at 16% and closers at 13%. 42% of the doors we measured had a leaf-to-frame gap over 4mm (156 of 371). Hinges drop, closers weaken and frames move every time a busy door slams, so busy doors need checking more often.
The good news: 95% of failed doors were repaired, not replaced (140 of 147 doors across three programmes). Catching faults early keeps repairs small. Full figures are on our fire door inspection statistics page, and our fire door repairs page explains what a typical fix involves.
The fire and rescue service can issue an enforcement notice. If the failure puts people at risk of death or serious injury, it is a criminal offence under Article 32 of the Fire Safety Order, with an unlimited fine or up to two years in prison.
Breaching Regulation 10 can be the same offence where it puts people at risk. In HMOs, the council can also act under the Housing Act 2004, with a fine or civil penalty and a risk to the licence. In care homes, CQC can act where premises are not safe or properly maintained.
Updated October 2026 by Sebastian Grabowski, DC Fire & Security. We inspect and repair fire doors across Bedfordshire, Hertfordshire, London, the Thames Valley and the East Midlands. Our own figures: fire door inspection statistics 2026.
Inspections follow BS 8214 and the government's fire door guidance. Repairs and new doorsets that need a third-party certificate are done by our BM TRADA Q-Mark certificated contractors, and fire stopping by our FIRAS-certificated contractors. Every job ends with photos and a report for your fire safety file.