Only blocks of flats with a top storey above 11 metres have fixed legal intervals: communal fire doors at least every 3 months and flat entrance doors at least every 12 months, under the Fire Safety (England) Regulations 2022. Everywhere else the fire risk assessment sets the interval, and government guides suggest checking every fire door monthly.

By Sebastian Grabowski, DC Fire & Security, Luton. Updated November 2026.

How often do fire doors need inspecting in each type of building?

Only blocks of flats over 11m have fixed legal intervals. Every other building relies on its fire risk assessment (FRA), and where no law sets an interval the table gives common practice instead.

BuildingWhich doorsHow oftenOften missed
Flats, top storey over 11mCommunal doors: corridors, stairs, lobbies, plant rooms and risersAt least every 3 months (law)Riser and plant room doors, and a written record of every check
Flats, top storey over 11mFlat entrance doorsAt least every 12 months, best endeavours (law)Recording refused access, and doors swapped by leaseholders
Flats, 11m and underCommunal and flat entrance doorsNo fixed legal interval. The FRA sets it. Common practice is routine checks every 1 to 3 months and a professional inspection every 6 to 12 monthsAssuming no checks are needed
HMOsRoom doors onto the escape route, kitchen, cellarNo fixed national interval. The FRA and licence conditions set it. Common practice is a check at each landlord visit and a professional inspection yearlyDisconnected closers, painted seals, keyed locks instead of thumb-turns
SchoolsAll fire doors, especially corridor and stair doorsNo fixed legal interval. The FRA sets it. Monthly staff checks are commonDoors wedged open between lessons, and old doors that were never fire doors
Care homesBedroom, corridor and compartment doorsNo fixed legal interval. The FRA sets it, usually with daily and monthly checks by staffHold-open devices that fail to release, and doors propped with furniture
Hotels, hostels and B&BsBedroom, corridor and stair doorsNo fixed legal interval. The FRA sets it. Monthly staff checks are commonEscape-route glazing and missing closers
Offices, shops, factories and warehousesAll fire doorsNo fixed legal interval. The FRA sets it. Monthly staff checks are commonStore and plant room doors, and doors wedged for deliveries
Student accommodationFlat, cluster, bedroom and corridor doorsIf it is a block of flats over 11m, treat it as the 3 and 12 month rule. Otherwise the FRA sets itClosers and seals damaged at move-in
Busy doors in any buildingCross-corridor and stair doorsAt least monthly, more often where damage is likelyClosers, hinges and seals wear fastest

The monthly check is a suggestion in government fire safety guidance for workplaces and care premises, not a rule, so treat it as the starting point and expect to explain doing less.

Is a fire door inspection a legal requirement?

A fixed schedule is law in one case only: residential buildings with a top storey over 11m, under regulation 10 of the Fire Safety (England) Regulations 2022, in force since 23 January 2023. Every other building still has a legal duty to keep fire doors in efficient working order and good repair (Fire Safety Order 2005, article 17).

Article 17 does not say how often. The fire risk assessment should set a frequency for each door type.

Regulation 10 also requires the responsible person in every block of flats with common parts, whatever its height, to tell residents to keep fire doors shut, not to tamper with closers and to report faults. New residents get this when they move in, and everyone gets a reminder at least every 12 months.

What is the difference between a routine check and a professional inspection?

A routine check is a quick visual look that trained staff can do, as the government guidance says, with no specialist or tools needed. A professional inspection is a door-by-door survey by a qualified inspector, usually every 6 to 12 months, that finds the faults a routine check misses.

Routine checks catch the obvious: a closer that no longer shuts the door, a missing seal, a wedge. A professional inspection, carried out in line with BS 8214, confirms the door is a genuine fire door, measures every gap against the 4mm industry limit, checks hinges, glazing and labels, and lists the repairs. Use our fire door inspection checklist for the routine checks and see fire door gap tolerances for the measurements.

Routine checkProfessional inspection
WhoCaretaker, site staff, fire warden or landlordA qualified fire door inspector
How oftenMonthly to every 3 months, or as the FRA saysUsually every 6 to 12 months, or after works
What is checkedDoor closes fully, seals present, no damage, nothing propping it openCertification, construction, every gap measured, closers, hinges, glazing, ironmongery, signage
RecordsDate, doors checked, faults found and reportedDoor-by-door report with photos, defects and the repairs needed

A professional fire door inspection of a small building typically starts from around £250 + VAT, and the price depends on the number of doors and the type of building.

What should make your interval shorter

The table gives common practice, not a target. Some doors fail faster than others, and the fire risk assessment should say so. Move to a shorter interval where one of these is true.

  • The door is on a busy route, with trolleys, deliveries, beds, buggies or school corridors.
  • The building has a history of wedging, tampering or damage.
  • Doors have been decorated, refloored or altered recently.
  • Tenants or occupants change often, as in student housing and HMOs.
  • The last inspection found a high number of faults.
  • The door is held open on a device, because the release has to work every time.

A quiet door in a small office can wait longer than a corridor door in a school. Say so in the fire risk assessment and write down why.

Events that call for an extra check

Intervals are not the only trigger. Inspect sooner, whatever the calendar says, after any of these:

  • Building work, refurbishment or new flooring that touched doors or frames.
  • A change of managing agent, landlord or tenant, so you start from a known baseline.
  • A failed check or a failed fire alarm test where a door did not release.
  • Doors being moved, re-hung or having new ironmongery fitted.
  • A report of damage, such as a door hit by a trolley or kicked in.

After repairs, have each door re-checked against the original fault. That is quicker and cheaper than waiting for the next full cycle.

Why do fire doors fail between inspections?

Because doors wear out with use. In our inspections, 72% of fire doors needed at least one repair on a first visit (339 of 470 doors, September 2025 to October 2026).

Across 448 doors, gaps and alignment were the biggest fault at 39%, followed by missing, damaged or painted seals at 35%, threshold and drop seals at 16% and closers at 13%. 42% of the doors we measured had a leaf-to-frame gap over 4mm (156 of 371). Hinges drop, closers weaken and frames move every time a busy door slams, so busy doors need checking more often.

The good news is that 95% of failed doors were repaired, not replaced (140 of 147 doors across three programmes). Catching faults early keeps repairs small. Full figures are on our fire door inspection statistics page, and our fire door repairs page explains what a typical fix involves.

What should the records show?

Each record should show the date, who checked, which doors were checked and what was wrong. For flat entrance doors in blocks over 11m, regulation 10 also requires you to record the steps taken to get access, including any refusal.

Records are your evidence. A fault that appears on three checks in a row with no repair is a red flag for any enforcing officer. Our demo inspection report shows what a full door-by-door record looks like.

  • Date and name of the person checking
  • Every door checked, by location or door number, including any you could not get to
  • Result per door: pass, or the fault found
  • Photos of each defect
  • Action: who is repairing it and when it was fixed
  • Flat doors: letters sent, dates offered and any refusal

Making the schedule work

A schedule that lives in one person's head fails when they go on leave. Keep a door schedule with the location, rating and type of each door, and check against it. Split the work into a routine round by trained staff, with a professional inspection at a longer interval to catch what a routine round misses. What a fire door inspector checks shows what the professional version adds. For where responsibility sits in a block, see who is responsible for fire doors in flats.

A fire risk assessment is a separate service from a door inspection. A door inspection does not replace it, and an assessment does not replace measuring every door. Our guide to fire door inspection vs fire risk assessment explains the difference.

What happens if you do not check your fire doors?

The fire and rescue service can issue an enforcement notice. If the failure puts people at risk of death or serious injury, it is a criminal offence under article 32 of the Fire Safety Order, with a fine on summary conviction or, on conviction on indictment, a fine, up to two years in prison, or both.

Breaching regulation 10 can be the same offence where it puts people at risk. In HMOs, the manager must keep the means of escape in good order and repair under regulation 4 of the 2006 management regulations, and the council can act under the Housing Act 2004.

Book the yearly inspection

We inspect blocks of flats, HMOs, schools, care homes and offices on a yearly or six-monthly cycle, with the same door numbers each time so the reports compare. See fire door inspections for what the visit covers and what the report looks like, or send the address and roughly how many doors for a price.

Sources

Frequently Asked Questions

Do fire doors really need checking every 3 months?
By law, only communal fire doors in residential buildings with a top storey over 11m. Elsewhere, the fire risk assessment sets the interval.
Is a monthly fire door check a legal requirement?
Not in most buildings. Government guides for workplaces and care premises suggest a monthly check of fire doors, but only blocks of flats over 11 metres have a legal interval. The fire risk assessment should set yours and you should expect to explain a longer one.
How often should fire doors be inspected in flats under 11m?
No law fixes it. The fire risk assessment sets the frequency. A common approach is a routine check every 1 to 3 months and a professional inspection every 6 to 12 months.
How often should fire doors be checked in the workplace?
As the fire risk assessment says. Monthly staff checks are common, with a professional inspection every 6 to 12 months for larger sites.
Does a new building need its fire doors inspected?
Yes, in time. Doors move once they are in use, so build the first inspection into the handover records and then follow the schedule in the fire risk assessment.
Should fire doors be inspected after refurbishment?
Yes. Flooring, decoration and new ironmongery all change gaps, seals and closers, so check the doors before the building is reoccupied.
Can I check fire doors myself?
Yes, for routine checks. The government guidance says the regulation 10 checks are simple and basic and can be done by trained staff. Repairs and periodic inspections should be done by a competent person.
Can the same person do the routine check and the annual inspection?
They can, but an independent professional inspection gives you a second opinion on doors your staff walk past daily. Many responsible persons use staff for the routine round and a professional for the baseline.
Who is responsible for fire door checks in a block of flats?
The responsible person, usually the freeholder, landlord or managing agent.
What if a resident refuses access to check their flat door?
Record every attempt and the refusal, and offer a range of times. The government guidance says legal action might need to be considered if a resident keeps refusing.

Send us photos or your report

Email your report or photos to info@dcsecurity.co.uk, or use the form. We usually come back with a fixed price the same day. Luton, Bedfordshire, Hertfordshire, Buckinghamshire and London.