What should a quarterly fire door check log include?

A quarterly fire door check log should record the date, who checked, each door's reference and location, a pass or fail for the closer, gaps, seals, hinges, glazing and signs, any fault, who was told and when it was fixed. In England, regulation 10 requires communal fire doors in buildings over 11 metres to be checked every three months.

By Sebastian Grabowski, DC Fire & Security, Luton. Updated November 2026.

What the law asks for

Regulation 10 of the Fire Safety (England) Regulations 2022 covers buildings with two or more sets of domestic premises. Where the building is over 11 metres, measured to the top storey, the responsible person must check the fire doors in the communal areas at least every three months. The check has to include confirming that the self-closing devices work.

The regulation does not give you a form. It says what must be checked and how often, and it requires records of the flat entrance door checks, including any attempts to get in that were refused. For communal doors the regulation is silent on paperwork, but a check with no record is very hard to prove later, so keep a log either way.

The log, column by column

Copy this layout into a spreadsheet or print it as a sheet for the clipboard.

ColumnWhat to write
Door referenceThe same number as on your fire door register, for example 2F-04
LocationFloor, corridor or stair, and which side of the door you are describing
Date and timeWhen you looked at it, not when you typed it up
Checked byFull name of the person, so they can be asked about it
CloserPass if it shuts the door fully from wide open and latches it. Fail if it stalls, slams or leaks oil
GapsPass if the gaps look even all round and you cannot see daylight at the edges. Fail if they are visibly wide or tight
SealsPass if the strips are present, unbroken and not painted over. Fail if missing, torn or clogged with paint
HingesPass if all are firm with every screw in place. Fail if loose, sagging or missing a screw
Leaf and framePass if free of holes, splits and large cracks. Fail if damaged or a hole has been cut for cables
GlazingPass if the glass and beads are intact. Fail if cracked, loose or replaced with something unmarked
SignsPass if the Fire door keep shut sign is there on the correct side. Fail if missing or defaced
Held openYes or no. Any wedge, hook or door stop is a fail
Fault and actionWhat is wrong, with a photo number
Reported toWho you told and when
Fixed onDate repaired, and who did it

How to do the check without missing things

Walk the building in the same order every quarter, so a door is never skipped. Open each door fully, let go, and watch it close. A door that needs a push to latch is a fail, even if it does eventually click.

Look down the closing edge and along the top. Even gaps are the thing to look for. A door that has dropped on its hinges shows a wedge shaped gap at the top and a tight bottom corner, and the fix is rarely a quick adjustment. Our guide on fire door gap tolerances explains the limits.

Run a finger along the seal. Layers of paint are the commonest reason a strip stops working. If you are unsure about a door, mark it as a fail for a competent person to look at. It is much easier to downgrade a door than to explain a missed one.

What goes wrong with these logs

Most logs fail the same few ways.

  • The same person ticks every door as a pass in the same ten minutes, with no faults noted for a year.
  • Doors are described by a nickname such as the green door, and nobody can tell which one it is a year later.
  • A fault is logged and nothing happens. A log that records the same broken closer for four quarters is evidence against you.
  • Flat entrance doors are left out because nobody has the access. Regulation 10 asks for best endeavours and a record of each attempt, so log the knock, the letter and the date.

A quarterly check is a look around by someone in the building, not a full inspection. A competent fire door inspector examines the door in detail and reports against the standard, which is a separate job. Read our page on fire door inspections for what that covers, and our fire door inspection checklist for the full list of points.

When to bring in a specialist

Call a competent person when a door fails on the closer, the gaps, the frame or the leaf. Our fire door repairs page explains what we do. Where the faults point to a door that cannot be repaired, see repair or replace.

Sources

Frequently Asked Questions

How often should fire doors be checked?
Communal fire doors in a building over 11 metres must be checked at least every three months under regulation 10 of the Fire Safety (England) Regulations 2022. Flat entrance doors in those buildings must be checked at least every 12 months, using best endeavours to get access.
Who can do the quarterly check?
Regulation 10 does not name a qualification, so the responsible person decides who is competent. A trained caretaker or site manager can do it, as long as they know what a failing door looks like and have a way to report it. A full inspection of the door is a different job and is better done by a specialist.
Does the log need to be on paper?
No. The regulations do not say what format records must take. A spreadsheet or a phone app is fine if each entry has a date, a named person and the door it refers to, and if it can be shown on request.
What do I do when a door fails?
Log the fault, report it to the person who arranges repairs and book a competent person to fix it. Until it is fixed, tell residents or staff and keep an eye on the door, because a door that will not close or has a damaged seal is not protecting the escape route.