Fire Stopping Case Study

Fire Stopping Case Study: Health Club Plant Room in Luton

We replaced non-compliant expanding foam in the main electrical switchroom of a health club and spa in Luton. Our own crew sealed 10 service penetrations through the ceiling soffit with a tested, third-party certificated Nullifire batt and sealant system, labelled and photographed every seal, and issued a completion report and certificate, all in one visit.

By DC Fire & Security, Luton. Client details withheld.

The job at a glance

WhatDetail
BuildingHealth club and spa, Luton
RoomMain LV electrical switchroom (plant room)
ProblemExpanding foam around cables passing through the ceiling soffit
Services sealedCable trays, trunking and main supply cables
Seals10, each with its own numbered label
ProductsNullifire FB750, FS712, FS702 and FS709
HandoverPhoto report, seal schedule and completion certificate
Time on siteOne visit, with the club open as normal

The problem we found

The main power for the whole club comes up through this room. Cable trays, steel trunking and heavy supply cables pass through the ceiling soffit above the switchgear, and every one of those openings is a hole in a fire-resisting construction. If fire starts in a switchroom, those openings are the easy route for fire and smoke into the floor above.

The openings had been filled with ordinary expanding foam. Foam like this is not a tested fire stopping system for cable penetrations, so there was no evidence it would hold back fire or smoke for any length of time. It also gave the owner nothing to show an inspector: no product record, no photos and no label.

Before and after

The same openings, photographed before we started and after the work was finished. Seal labels are blurred in these photos to keep the client's details private.

Cable trays and trunking at the ceiling

Before: cable trays and trunking passing through the plant room ceiling, with orange expanding foam stuffed around them
Before: cable trays and trunking passing through the plant room ceiling, with orange expanding foam stuffed around them
After: the same cable trays and trunking sealed with coated fire batt and sealant, each seal labelled
After: the same cable trays and trunking sealed with coated fire batt and sealant, each seal labelled

Main supply cables above the switchgear

Before: main supply cables entering the ceiling above the switchgear, sealed only with expanding foam
Before: main supply cables entering the ceiling above the switchgear, sealed only with expanding foam
After: main supply cables sealed with Nullifire coated batt boxed around the soffit, with labelled seals
After: main supply cables sealed with Nullifire coated batt boxed around the soffit, with labelled seals

Tray and cable openings across the room

Before: open and foam-filled tray and cable openings in the plant room ceiling
Before: open and foam-filled tray and cable openings in the plant room ceiling
After: tray and cable openings closed with fire batt and sealant, each seal numbered
After: tray and cable openings closed with fire batt and sealant, each seal numbered

What we did

  • Protected the room. The switchroom was secured, and the floor and live equipment covered before any work started.
  • Removed the foam. The old expanding foam was cut out from around the cables, trays and trunking and taken away.
  • Fitted the batt. Coated fire batt was cut to fit each opening and bonded in place around the services.
  • Sealed every edge. Fire-rated sealants closed the edges of the batt and the small gaps around cables and conduits.
  • Labelled and recorded. Each seal got its own numbered label and was photographed before we left.

All of it was done in one visit by our own fire stopping crew, with the club open and members using it as normal.

Close-up of fire batt and sealant fitted tightly around the main supply cables, with the seal label above
Close-up of fire batt and sealant fitted tightly around the main supply cables, with the seal label above
Conduits passing through a fire batt seal finished with graphite intumescent sealant
Conduits passing through a fire batt seal finished with graphite intumescent sealant

Products used

The whole room was sealed with one manufacturer's system, so every part of each seal is meant to work together. These are tested, third-party certificated fire stopping products, installed to the manufacturer's details for each type of service.

ProductWhat it does here
Nullifire FB750 Intubatt 2Coated mineral fibre fire batt that closes each opening
Nullifire FS712 IntucoatAblative coating used with the batt system
Nullifire FS702 IntumasticAcrylic fire sealant for the batt edges and the gaps around services
Nullifire FS709Graphite intumescent sealant around conduits and smaller services

Using a single system matters. Mixing a batt from one maker with a sealant from another usually means neither maker's test evidence covers the finished seal.

How every seal is recorded

Fire stopping is hidden work, and in a few years nobody remembers who did what. So we record every seal in the same way:

  • A numbered label on the seal itself. This job used DC-FS-00001 to DC-FS-00010. Each label shows the location, the opening size, the product system, who installed it and when it should next be inspected.
  • Photos of every seal. Taken on site and filed against the seal number, so anyone can match a label on the ceiling to a photo in the report.
  • A seal schedule and completion report. A table of all 10 seals with their locations, services and products, plus the before and after photos.
  • A completion certificate. A signed certificate for the building's fire safety file, ready for the fire risk assessor, insurer or building manager.

If a contractor later runs a new cable through one of these seals, the label tells them it is fire stopping, and the report shows what it looked like when it was handed over.

What this means for your building

Plant rooms, riser cupboards and ceiling voids are where we most often find foam, open holes or mixed products. If your fire risk assessment mentions fire stopping, or a contractor has run new services through a wall or ceiling, the openings are worth checking. A fire stopping survey finds and photographs them, and our fire stopping service puts them right with tested systems. Where you need to know what is hidden behind linings, see intrusive fire stopping investigations.

Send us the fire risk assessment action or a few photos of the openings using the quote form, or call 01582 227 123. We price fire stopping per job, from photos or a short survey.

Frequently Asked Questions

Why is expanding foam not acceptable as fire stopping?
Ordinary expanding foam is not a tested fire stopping system for cable or pipe penetrations, so there is no evidence it will stop fire and smoke. Fire stopping has to be a product system tested for that kind of service, opening and wall or floor, installed to the manufacturer's details. The difference is explained in fire stopping vs fireproofing.
Can fire stopping be done in a live plant room?
Yes. In this switchroom we secured the room, protected the floor and the live equipment, and worked around the cables without disturbing them. The club stayed open throughout, and the work was finished in one visit.
What paperwork do you get at the end of a fire stopping job?
You get a numbered label on every seal, a completion report with before and after photos and a seal schedule, and a signed completion certificate for the fire safety file.
How long does fire stopping a plant room take?
This room, with 10 openings, took one visit. Time on site depends on how many openings there are, how big they are, how much old material has to come out and how easy the access is, so we confirm it after seeing photos or the room.