Yes, but only with a device that lets the door close automatically when the fire alarm sounds or a smoke detector operates, such as an electromagnetic holder or a free-swing closer. Wedges, hooks, chairs and fire extinguishers are never acceptable. A held door must also close fully into its frame once it is released.
By Sebastian Grabowski, DC Fire & Security, Luton. Updated November 2026.
Wedging is not a named offence on its own, but it can breach the Regulatory Reform (Fire Safety) Order 2005. Article 17 requires the responsible person to keep fire safety measures in efficient working order and good repair.
Failing to meet that duty is an offence where it puts people at risk of death or serious injury in a fire. Article 32 sets the penalty as a fine on summary conviction, or on conviction on indictment a fine, up to two years in prison, or both.
A fire door only works when it is shut. It holds back fire and smoke for 30 or 60 minutes so people can get out along the escape route. A wedged door leaves a hole in that fire wall, often right on the corridor people need to use.
Enforcement usually starts with advice or an enforcement notice from the fire and rescue service. Prosecution is kept for serious or repeated failures, but a wedged door found after a fire is hard to defend. The Fire Safety (England) Regulations 2022 also require the responsible person of a block of flats to tell residents to keep fire doors shut when not in use.
A wedged door is nearly always a symptom. Someone has a reason, and until the reason is dealt with the wedge comes back. Work out which of these applies before choosing a device.
| Why the door is wedged | What is really wrong | What to do |
|---|---|---|
| The door is too heavy to push | Closer set too strong, or the wrong power size for the leaf | Adjust the closer, or fit a free-swing closer |
| Trolleys and deliveries pass all day | The door is on a busy route | Hold-open device linked to the alarm |
| The door slams and the noise annoys residents | Closer sweep speed set too fast | Slow the sweep and keep enough latch action |
| Staff want air through a hot room | No ventilation option | Sort out the ventilation, never the door |
| A resident needs the door open for care | Mobility or care need | Free-swing closer, agreed in the fire risk assessment |
A hold-open device on a door that nobody has wedged is worth a look as well. It may have been fitted years ago and never tested since.
There are four common lawful options: an electromagnetic door holder, a free-swing closer, a hold-open closer, and an acoustic (sound-activated) device. All of them release the door when the fire alarm operates.
Electrically powered hold-open devices and free-swing closers are covered by BS EN 1155. How they are triggered by the fire alarm is covered by BS 7273-4. The closer itself should meet BS EN 1154. A hold-open arm that stays put until someone pushes it is a wedge built into the closer, not a lawful device.
| Device | How it releases | Best suited to | Watch out for |
|---|---|---|---|
| Electromagnetic holder (wall or floor magnet) | Fire alarm cuts power, magnet lets go | Busy corridors in buildings with a fire alarm | Needs wiring to the alarm panel |
| Free-swing closer | Door swings freely, closer engages on alarm or power loss | Flat entrances, care homes, people who struggle with heavy doors | Needs an alarm or detector link to work |
| Hold-open closer | Magnet built into the closer arm, releases on alarm | New installs where a wall magnet does not fit | Same alarm wiring as a magnet |
| Acoustic device | Listens for the alarm sounder, then releases | Retrofits where wiring is difficult | Battery checks; useless if no alarm sounds nearby |
| Door closer delay device | Delays closing for a set time, then closes | Wheelchair users and slow walkers passing through | Not a hold-open; the door still closes on its own |
Yes. Every lawful hold-open device relies on a fire alarm, a smoke detector or the sound of a sounder to release the door. With nothing to trigger it, the door should simply be left to self-close.
This catches out small premises and many blocks of flats with a stay-put strategy. If there is no communal fire alarm, there is nothing to tell a magnet or acoustic device to let go. An acoustic device fitted in a corridor where no sounder ever goes off is just an expensive doorstop.
Some free-swing closers can be linked to their own smoke detector. That can suit a flat entrance door in a block with no communal alarm, as long as the fire risk assessment agrees. Communal corridor doors in those blocks should stay closed.
Corridor and lobby doors in a block of flats can be held open on magnetic devices only where smoke detectors would close them, according to the government's fire door guidance. Flat entrance doors should be self-closing and kept shut.
The guidance says plant room and service cupboard doors may be self-closing or kept locked shut. Where a resident needs the flat door open, for mobility or care reasons, a free-swing closer is the usual answer, agreed with the responsible person. The guidance also says that when a held door is checked, you should use the test button rather than pulling the door off the magnet.
Fitting a device is the easy part. The failures we see are on the release. A held door has to let go and close fully every time the alarm sounds, so test it as part of the routine alarm test and watch it happen.
A door that stays open after the alarm sounds is worse than a door that is never held, because everyone assumes it will close.
Check that held doors release and close fully every time the fire alarm is tested, usually weekly. The release should also be tested as part of the alarm's cause-and-effect checks at each service.
| Check | How often | Who |
|---|---|---|
| Held doors release and close into the frame | Each fire alarm test, usually weekly | Site staff or the responsible person |
| Acoustic device battery and release | As the maker recommends | Site staff |
| Release tested in cause-and-effect checks | At each alarm service | Fire alarm engineer |
| Communal fire doors checked (buildings over 11m) | At least every 3 months | Responsible person |
| Full fire door inspection, closer and seals included | Set by the fire risk assessment | A qualified inspector |
It is recorded as a fault on the fire door inspection report, and the reason behind it is fixed. In our inspection data, self-closer faults were found on 13% of 448 doors, and a badly set closer is one of the main reasons people wedge doors.
Often the fix is simple. A closer that slams or is too heavy can be adjusted or replaced. Where the door genuinely needs to stand open, a hold-open device linked to the alarm is the lasting answer. See our guide to fire door closers and our fire door inspection statistics, and use the fire door inspection checklist to test a held door during a routine check.
If an inspection has flagged wedged or damaged doors, our failed fire door inspection guide explains the next steps, and fire door repairs covers the work itself.
In a small building or a block with no communal alarm, there may be nothing to release the door. In that case the door should close itself, and the fix for a heavy door is a better closer, or a free-swing closer on its own smoke detector if your fire risk assessment agrees.
A fire door inspection records every wedged door, tests each closer and hold-open device, and gives you a list of what to fix, door by door. If doors need new closers or hold-open devices linked to the alarm, our fire door repairs team fits them. We inspect blocks of flats, HMOs, schools, care homes and offices; send the address and roughly how many doors for a price.
Email your report or photos to info@dcsecurity.co.uk, or use the form. We usually come back with a fixed price the same day. Luton, Bedfordshire, Hertfordshire, Buckinghamshire and London.
Send photos for a fixed price · No obligation · Response within 24 hours